Skip to product information
C-TEC CFP AlarmSense panel CFP702-2 CFP704-2 CFP708-2
£247.11
Sale price
£247.11
Regular price
Model number: CFP702-2
C-TEC CFP AlarmSense two-wire CIE. Heads, AlarmSense call points and AlarmSense sounders share one pair per zone. Do not mix 4-wire conventional heads on these zones.
| Model | Zones | List |
|---|---|---|
| CFP702-2 | 2 | £247.11 |
| CFP704-2 | 4 | £306.67 |
| CFP708-2 | 8 | £386.00 |
- LPCB EN54-2 / EN54-4
- Four conventional sounder circuits still on the board
- Up to 25 detectors or 32 detectors + MCPs per zone (AlarmSense loading)
- 500 m max per zone circuit
- EOL devices supplied one per zone
- CFP760 repeaters via CFP761
- Two 12 V 3.2 Ah batteries not included
- 380 × 235 × 96 mm
CFP708-2 was truncated on the public April 2025 list extract; £386.00 follows the 4-wire 4→8 step until the printed line is confirmed.
Documentation & specifications
| Size / rating | 0 |
|---|